Partial Discharge measurements for failure diagnosis on an oil-filled high voltage cable

http://odoo.e-cigre.org/web/image/product.template/5728/image_1920?unique=f240640

This paper reports about the experience with monitoring of partial discharges (PD) on an oil-filled high voltage cable which is part of the 110 kV distribution network in the city of Hamburg. The nearly 6 km long oil-filled cable system was switched off due to an internal electrical fault without breakdown. The fault did not cause any internal breakdown but partial discharge. Thus the fault localization using impulse reflection measurement was not possible. In order to detect the internal fault, resonant voltage tests with concurrent PD measurement were accomplished. Due to the length of the cable and the high attenuation of PD impulses in oil-filled HV cables it was not sufficient to only use one PD sensor at the cable termination. Thus, for fault detection, additional PD sensors were…